How do I change direction of a motor using a ACH550 keypad?

Q. How do I change direction of a motor using a ACH550 keypad?

A. On the ACH550 VSD units, the direction can be selected via the keypad and rotation locked in parameter 10.03, FWD – REV or REQUEST.

However if you wish to switch from forward to reverse, this can only be selected via a DI, Parameter 10.01 set to DI 1,2. Start /Stop on DI1 on run off stop & DI2 FWD / REV off FWD and on REV.

10.01 DI1,2

10.03 REQUEST

 

If you need technical support, email us at techsupport@quantum-controls.co.uk or call us 24/7 on 0330 9000 247.