• £0.00 GBP
    0


  1. Overview
  2. Data
  3. Tools

Overview

Power converter modules DCS800-S0x are compactly designed to be installed into a customer's own cabinet. Modules enables OEM's, system integrators and panel builders to build their own drive solutions.

Compact and powerful

  • Single modules up to 5 200A
  • DC-voltage up to 1 500VDC,
  • AC-voltage up to 1 200V
  • High-power solutions up to 20 000A
  • hard parallel (without DC-chokes)
  • 12puls parallel, serial and sequential

Designed to ease your life

  • Comfortable and intuitive assistants
  • Autotuning of all internal controllers
  • Fully integrated field supply

Scalable to fit any application

  • Wide range of plug-on option modules
  • Peer-to-peer communication
  • Remote control by Ethernet

Programmable to meet application needs

  • Supported of all five IEC61131 languages
  • Standard programming tool CoDeSys
  • Pre-configured functions

Documents of DCS800, also documents of DCS500 and of DCS600

Documentation will be found after selecting the device in field
"Please select categories"


Brochure

ABB Drives-Product Guide English - 0.62 MB – pdf

DCS800 Technical Catalogue English - 1.02 MB - pdf

Manual

DCS800 Quick Guide
English - 14.26 MB - pdf

Installation in accordance with EMC
English - 0.51 MB - pdf

Mains supply

Voltage - power part, 3-phase
Voltage Deviation
Rated Frequency

230V to 1000V in acc. with IEC 60038, higher voltage is available on request. +/- 10% continuous 50Hz or 60Hz

Voltage - field exciter
Voltage deviation
Frequency range

110 to 500V, 1 ph for units 6...50Adc +/- 10% continuous 50Hz or 60Hz

Voltage - aux. supply, 1-phase
Voltage deviation
Frequency range

115V / 230V in acc. with IEC 60038
-15% / +10%
45Hz to 65Hz

Voltage - fan supply

115V/230V, 1 ph ... 690V, 3 ph depending on frame sizes.

Degree of protection
as DCS800-A Enclosed Conv.
as DCS800-E Panel Solution
IP 00
IP20 / IP21 / IP31 / IP41
IP20

DC Outputs

 

DC voltage

The maximal DC voltage is depending on supply voltage and converter type (2Q or 4Q). If a 2Q unit is also used in regenerative mode, please use also the values of the 4Q column. The following classes are available with the recommended DC voltage:


AC supply

DC voltage

Description: http://www04.abb.com/icons/ecblank.gif

2Q

4Q

230V

265V

240V

400V 465V 415V

500V

580V

520V

600V

700V

625V

690V

800V

720V

790V

915V

820V

990V

1160V

1040V

1200V

1380V

1235V

   

DC current

According rated current of frame sizes:

20 ... 260A

D1, D2 with supply up to 525Vac

350 ... 1000A

D3, D4 with supply up to 525Vac/600Vac

900 ... 2000A

D5 with supply up to 690Vac

1900 ... 3000A

D6 with supply
up to 800Vac

2050 ... 5200A

D7 with supply
up to 990/1200Vac

> 5200A

D7 with supply
up to 990/1200Vac

Higher current available on request.

Please find more details also about overload capability in DCS800 Technical Catalogue.

   

DC field voltage

Max. field voltage 110V to 500V, depending on supply voltage and field exciter unit.

 

6/15/20/25A - Field exciter onboard of D1/D2/D3/D4

25A Internal with FEX-425-INT for D5 as option

35A Field exciter DCF80x (external)

> 35A on request

   

DCS500 and DCS600 products

for detailed data please see DCS500B System Description or DCS600 System Description

Tools for DCS800

0DCS800 panel

The control panel communicates with the power converter DCS800

  • Large display
  • Two soft keys
  • Help function
  • Multilingual
  • Startup Assistant
  • Shows actual values in physical values
  • Copy and compare function for parameters

DriveWindow light

DriveWindow light (short DWL), version 2.6 onwards, is an easy-to-use start-up and maintenance tool for DCS800 under WindowsTM 2000/XP. The connection to the drive needs a free serial port from PC and standard RS232 cable. All DCS800 drives are equipped with DriveWindow Light.

The tool has the following features:

  • Viewing and setting parameters in offline and online mode
  • Editing, saving and downloading parameters
  • Comparing parameters
  • Graphical and numerical signal monitoring
  • Local operation
  • Start-up assistant (add-on for DCS800)
  • DWL AP tool (add-on for DCS800)

DriveWindow light

DriveWindow, version 2.2 onwards for DCS800, is the start-up and maintenance PC program for DCS600, which can be run on laptop PC under Windows 2000TM or Windows XPTM. CD ROM drive (for installation) and PCMCIA slot are necessary. The Drive Window package contains the installation CD ROM, NDPA-02 PC card, NDPC-12 connector between PC card and optical fiber cable and 10m plastic optical fiber cable. DCS800 requires the SDCS-COM-8x option. A monitoring network connection is also possible.

The tool has the following features:

  • Parameter programming
  • Feedback display and analysis
  • Local operation
  • Parameter uploading, saving as file and downloading, comparing with
  • Saved files
  • Fault detection for trouble-shooting
  • Monitoring and data logger
  • Fault logger
  • OPC interface

ControlBuilder DCS800

ControlBuilder DCS800 is based on the IEC61131-3 standard program CoDeSys 2.3. With ControlBuilder DCS800 it is possible to develop new functions, e.g. winders, decentralized controls and safety functions, directly in the drive. The application program is stored on the Memory Card (MC), which is plugged into the drive. If desired, the source code can also be stored and can be password protected against unauthorized access.

Tools for DCS500 and DCS600

CDP-312 panel

The control panel communicates with the converters DCS500B and DCS600

DDCTool 4.0

The PC program DDCTool, version 4.x, is the start-up and maintenance program for DCS500, which can be run on laptop PC under Windows 2000TM or Windows XPTM. CD ROM drive (for installation) and PCMCIA slot are necessary. The DDCTool package contains the installation CD ROM, SNAT624 PC card, Connector to drives with 10m plastic optical fiber cable. On drive side the optical fiber cable will be connected as point-to-point to the SDCS-COM-5 option of DCS500.

DriveWindow

The PC program DriveWindow is the start-up and maintenance PC program for e.g. DCS600, which can be run on laptop PC under Windows 2000TM or Windows XPTM. CD ROM drive (for installation) and PCMCIA slot are necessary. The Drive Window package contains the installation CD ROM, NDPA-02 PC card, NDPC-12 connector between PC card and optical fiber cable and 10m plastic optical fiber cable. A monitoring network connection is also possible.

 

There are no products matching the selection.